Control toroidal transformers
01
Mono-phase toroidal transformers
Control toroidal transformers
- Control transformers – compliant to SR EN 61558-2-2.
These transformers have an input rated voltage up to 1000 Vac, the rated frequency up to 50 Hz, and a rated output not exceeding 1000 VA. - They are defined by a specific parameter which is the instantaneous maximum output, this being the maximum power produced temporarily, when the transformer is supplied with the rated input voltage, rated frequency, load power factor is 0,5 and the secondary voltage is no less than 95% from rated value.
- The transformers produced by PETRA have an instantaneous maximum output which is 25% more than the rated output.
Tehnical data Control toroidal transformers
| Power [VA] | Dmax [mm] | H [mm] | Weight [kg] | dU [%] | DTmax (C) | Cooper losses [W/20C] |
No load losses [W] |
|---|---|---|---|---|---|---|---|
| 3 | 46 | 26 | 0.13 | 21.97 | 25 | 0.83 | 0.09 |
| 5 | 51 | 27 | 0.18 | 17 | 26 | 1.01 | 0.14 |
| 10 | 52 | 29 | 0.21 | 20.17 | 40 | 2.44 | 0.14 |
| 15 | 61 | 29 | 0.30 | 17.1 | 39 | 3.04 | 0.21 |
| 20 | 62 | 30 | 0.35 | 15.69 | 43 | 3.69 | 0.21 |
| 25 | 70 | 29 | 0.43 | 13.22 | 39 | 3.81 | 0.32 |
| 30 | 71 | 30 | 0.47 | 13.26 | 44 | 4.58 | 0.32 |
| 35 | 71 | 30 | 0.50 | 12.97 | 47 | 5.21 | 0.33 |
| 40 | 75 | 35 | 0.58 | 12.96 | 44 | 5.95 | 0.39 |
| 50 | 85 | 36 | 0.74 | 11.32 | 41 | 6.36 | 0.51 |
| 63 | 89 | 36 | 0.74 | 11.32 | 41 | 6.39 | 0.51 |
| 80 | 90 | 37 | 0.98 | 9.55 | 47 | 8.51 | 0.61 |
| 100 | 90 | 45 | 1.16 | 9.02 | 51 | 9.95 | 0.75 |
| 120 | 100 | 44 | 1.37 | 8.74 | 50 | 11.56 | 0.97 |
| 150 | 111 | 46 | 1.68 | 7.80 | 48 | 12.82 | 1.23 |
| 200 | 123 | 48 | 2.15 | 7.24 | 49 | 15.75 | 1.54 |
| 250 | 130 | 46 | 2.48 | 6.47 | 51 | 17.44 | 1.82 |
| 300 | 126 | 55 | 2.92 | 5.72 | 51 | 17.44 | 1.82 |
| 350 | 136 | 56 | 3.37 | 5.43 | 50 | 20.22 | 2.76 |
| 400 | 138 | 58 | 3.64 | 4.91 | 51 | 20.80 | 2.73 |
| 450 | 143 | 58 | 4.01 | 4.70 | 52 | 22.36 | 3.00 |
| 500 | 145 | 59 | 4.23 | 4.54 | 54 | 23.73 | 3.01 |
| 630 | 161 | 59 | 5.26 | 4.08 | 53 | 29.96 | 3.89 |
| 750 | 176 | 60 | 6.24 | 3.98 | 53 | 29.96 | 3.89 |
| 850 | 178 | 61 | 6.66 | 3.73 | 55 | 33.08 | 4.77 |
| 1000 | 172 | 69 | 7.68 | 3.11 | 54 | 32.17 | 6.22 |
The information presented above is typical data and can be changed without prior notice.
Other values are available on request.
Other Mono-phase toroidal transformers:
02
Three-phase toroidal transformers
Technical characteristics:
Open construction, impregnated
Voltage: on request
Frequency: 50-60 Hz
Protection class: IP 00. Electrical protection: I or II.
03
Custom made transformers
Please fill in this form in order to send us your offer request, an order or just to ask for our technical advice regarding your projects. If you need some other product than a toroidal transformer please specify the details in the "Other requests" box.
You will receive our answer within 24 hours.
See other products:
Alternative current power supplies
Applications, technical specifications, A.C. power supplies 220 V/ 110 V with toroidal transformers.
Inductors
DC Inductors
Mounting hardware
In order to mount the transformer right you need to read carefully the data on the label